H3G-TH lead acid battery monitoring system is equipped with battery thermal runaway warning, high-accuracy SOC/SOH monitoring, and comprehensive intelligent analysis of the battery. This battery monitoring system for lead acid battery can effectively ensure the safe operation of backup batteries in high-end data center computer rooms, petroleum and petrochemical systems, and rail transit systems.
Topology of H3G-TH Battery Monitoring System
Features of H3G-TH Lead Acid Battery Monitoring System Thermal runaway AI analysis and early warning
Advanced low power consumption design
AI data analysis
High-accuracy SOC/SOH
Function of H3G-TH Battery Monitoring System Thermal runaway
Charge/discharge current
String voltage
Float current
SOC/SOH
Cell voltage
Cell temperature
Ambient temperature
Intelligent equilibrium
Cell internal resistance
Specification of H3G-TH Battery Monitoring System Measuring content Range Accuracy Resolution Sting voltage 20¡«800V ¡À0.5% 0.1V Cell voltage 1.2V,2V,6V,12V ¡À0.1% 0.001V Cell internal resistance 50¡«65535¦Ì¦¸ ¡À2%£¨repetitive accuracy£© 1¦Ì¦¸ Temperature -5¡«+99.9℃ ¡À1℃ 0.1℃ Charge/Discharge current ¡À1500A ¡À1% 0.1A SOC/SOH ¡ª ¡À5% 1%